APPENDICES
-------------------
MELSEC-A
APPENDIX 5 Cautions on Editing Programs
This
section
gives matters
to
be attended in editing
the
sequence programs
stored in the A2C.
(1) Program reading
Read
the
programs stored in
the
A2C in combination of "parameters
+
main program" using
the
GPP/PHP/HGP.
(2)
Editing
with
the
GPP/PHP booted with
the
SW4GP-GPPA
Sequence programswritten with
the
SW3GP·GPP/SW3-HGPA or earlier
system disk can be edited.
If a sequence program written with
the
SW3GP·GPPA/SW3·HGPA or
earlier system disk is edited with
the
SW4GP-GPP, parameters remain
unchanged from those set with the SW3GP-GPPA/SW3·HGPA or earlier
system disk.
To
change
the
initial
setting
from
sequence
program
setting
to
parameter setting, use
the
remote terminal setting with parameters.
(3) Editing with
the
GPP/PHP/HGP
booted
with
the
SW3GP-GPPA/SW3-
HGPA or earlier system disk
Sequence programs written with
the
SW4GP·GPPA system
disk
can be
edited.
It is impossible to change remote terminal setting with parameters.
To change remote terminal setting, follow
the
procedures below.
(a) In case
the
software version
"C"
or earlier is used,
the
priority of
remote terminal setting of parameters is
higher
than
that
of
the
sequence program. Therefore. follow
the
procedures below:
1) Clear all parameters to defaults.
2) Set parameters other than defaults.
3) Add the initial setting program to
the
sequence program.
(b) In case the software version
"0"
or later is used,
the
priority of
remote terminal setting of the sequence
program
is
higher
than
that
of the
parameters.
Therefore, do
the
following:
1) Add
the
initial setting program by use of
the
sequence program.