174
(3) Instructions that do not operate normally during online change
When data are written to the CPU module in the RUN status, the following instructions do not operate normally.
Rise instruction
SCJ instruction
•STMR instruction
(a) Rise instruction
The rise instruction is not executed when the instruction is in the data written to the CPU module in the RUN
status, even if the execution condition (off on) is met.
The corresponding rise instructions are PLS and P.
Completion of
online change
END
1 scan
END END00 0
OFF OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON ON
X0 status
X0
M0
X0
M0
X0
M0
The rise instruction is not executed even
if the execution condition is off on.
[ PLS M0 ]
X0
A
A
OFF ON