3.15.1 Simultaneous monitoring from multiple programming tools
This function allows simultaneous monitoring from multiple programming tools connected to modules (such as a
CPU module and serial communication module). Creating a user setting system area allows high-speed
monitoring from multiple programming tools. (Setting a monitoring file for the host station is not required.)
(1) Setting for simultaneous monitoring from multiple programming tools
Create a user setting system area by the following procedure.
1. Open the "Format PLC Memory" screen.
[Online] [PLC Memory Operation] [Format PLC Memory]
2. Select "Program Memory" for "Target Memory".
3. Select "Create a user setting system area" in "Format Type".
4. Set the number of steps for the system area (in increments of 1K step) within the following range.
Only 1K step is available for each monitoring file from another station.
Maximum size of settable step System area for monitoring from another station
Maximum 15K steps Maximum 15
Programming tool
Programming tool
Monitor target