EasyManua.ls Logo

Mitsubishi Electric MELSEC-Q00U(J)CPU

Mitsubishi Electric MELSEC-Q00U(J)CPU
588 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
270
(7) Precautions
Do not perform the following operations during data backup.
Even when parameters that are backed up using contacts are booted to the Universal model QCPU whose
serial number (first five digits) is "10101" or earlier, parameters are ignored. In this case, even if the backup
start setup contact or backup start contact set in parameter is turned on, the operating status of the CPU
module does not change. (No diagnostic error is detected.)
When the data backup operation is ready, the CPU module stops the operations of the following functions.
The operations do not resume even after the data backup operation ends.
Data cannot be backed up while data logging is being executed. Stop the data logging processing, and then
start the data backup operation. For how to stop the data logging processing, refer to the following.
QnUDVCPU/LCPU User's Manual (Data Logging Function)
If the data backup processing is performed while the CPU module is locked with a security key, an error
occurs.
Insertion/removal of a memory card or SD memory card
Power-off of the CPU module
Reset
Refresh of network modules
Refresh of CC-Link IE Field Network Basic
Data link transfer
Auto refresh of intelligent function modules
Auto refresh of CPU shared memory
Simple PLC communication function

Table of Contents

Related product manuals