CHAPTER 4 DEVICES
4
4.2 Internal User Devices
4.2.10 Timer (T)
(6) Timer processing and accuracy
(a) Processing
When the OUT T or OUT ST instruction is executed, the on/off switching of the timer coil, current value
update, and on/off switching of the contact are performed.
In the END processing, the current timer value is not updated and the contact is not turned on/off.
X0
T0
K10
END OUT TO END
[Processing at execution of OUT T0 instruction]
[Ladder example]
Sequence
program
Processing
Coil ON/OFF
Current value update
Contact ON/OFF