412
(2) When an A series interrupt module is mounted
*1 The time-limit value of the internal timer is set by default. In the PLC system tab of the PLC parameter dialog box, the
value can be changed within the range of 0.5ms to 1000ms in increments of 0.5ms.
*2 This is available for multiple CPU system configuration.
*3 To use the intelligent function module interrupt, the intelligent function module setting (interrupt pointer setting) is
required in the PLC system tab of the PLC parameter dialog box. (For interrupt from an intelligent function module, refer
to Page 231, Section 3.22.)
*4 I50 has the highest priority (priority 6), and I255 has the lowest priority (priority 211).
*5 When an interrupt occurs, even if no interrupt pointer exists on the program, CAN'T EXECUTE(I) (error code: 4220)
does not occur.
*6 To use I49, do not execute any other interrupt programs (I0 to I48, I50 to I255) nor fixed scan execution type programs.
If executed, the interrupt program (I49) will not be executed at preset intervals.
I No. Interrupt factor Priority I No. Interrupt factor Priority
I0
Interrupt by an
interrupt module
(A1SI61)
1st point 224
I32 to
I44
-N/A-
I1 2nd point 225
I2 3rd point 226
I3 4th point 227
I4 5th point 228
I5 6th point 229
I6 7th point 230
I7 8th point 231
I8 9th point 232
I9 10th point 233
I10 11th point 234
I11 12th point 235
I12 13th point 236
I13 14th point 237
I14 15th point 238
I45
*2 *5
Multiple CPU
synchronous
interrupt
0.88ms 1
I15 16th point 239
I16
Interrupt by a
sequence-started
module
1st module 212
I46 to
I48
-N/A-I17 2nd module 213
I18 3rd module 214
I19 4th module 215 I49
High-speed
interrupt
0.1 to 1.0ms *6
I20 5th module 216
I50 to
I255
Intelligent
function module
interrupt
*3*4
/Interrupt by an
interrupt module
(A1SI61)
Specify an intelligent function
module or interrupt module
(A1SI61) in parameter.
6 to 211
I21 6th module 217
I22 7th module 218
I23 8th module 219
I24 9th module 220
I25 10th module 221
I26 11th module 222
I27 12th module 223
I28
*5
Interrupt by the
internal timer
*1
100ms 5
I29
*5
40ms 4
I30
*5
20ms 3
I31
*5
10ms 2