450
Detailed
Setting
Error Time
Output Mode
0403
H
Set whether to clear or hold the output
in case of a stop error in the control
CPU.
Clear/Hold Clear
Page 141,
Section 3.8
PLC
Operation
Mode at H/W
Error
4004
H
Set whether to stop or continue the
operation of the control CPU in case
of a hardware failure of the intelligent
function module.
Stop/Continue Stop
Page 142,
Section 3.9
I/O Response
Time
0405
H
Set a response time for the input
module, high-speed input module, I/O
combined module, or interrupt
module.
Input or I/O Mix: 1ms, 5ms, 10ms,
20ms, or 70ms
Hi. Input or Interrupt: 0.1ms, 0.2ms,
0.4ms, 0.6ms, or 1ms
Input or I/O
Mix: 10ms
Hi. Input or
Interrupt:
0.2ms
Page 139,
Section 3.7
Control PLC
0406
H
Set the control CPU for the
input/output modules and intelligent
function module.
PLC No.1, No.2, No.3, or No.4 PLC No.1
QCPU User's
Manual
(Multiple CPU
System)
Select PLC type -
Sets the model of the connected CPU
module automatically in the "I/O
Assignment" area by selecting the
module from the pull-down menu.
-Blank
Page 54,
Section 2.2.2
Select module -
Sets the model name, points, and
start I/O number of the selected
module automatically in the "I/O
Assignment" area by selecting the
module from the pull-down menu.
-Blank
Item
Parameter
No.
Description Setting range Default Reference