CHAPTER 2 APPLICATION OF PROGRAMMING
2
2.3 I/O Number Assignment
2.3.2 Setting I/O numbers
(d) When using AnS/A series compatible extension base units
When using the Q5B/Q6B in combination with the AnS/A series compatible extension base units,
QA1S5B, QA1S6B, and QA6B, take the following precautions.
Connect the extension base units in the order of the Q5B/Q6B, QA1S5B/QA1S6B, QA6B from
the closest position to the main base unit.
The QA1S51B does not have an extension cable connector (OUT) and therefore cannot be used in
combination with the QA6B.
Batch-assign I/O numbers of the modules mounted on the base units for each series: Q series A series
or Aseries Q series. Failure to do so will result in "SP.UNITLAY ERR.".
When the QA6ADP+A1S5B/A1S6B is used, refer to the following.
QA6ADP QA Conversion Adapter Module User's Manual
When the QA1S6ADP+A1S5B/A1S6B is used, refer to the following.
QA1S6ADP Q-AnS Base Unit Conversion Adapter User's Manual
QA1S6ADP-S1 Q-AnS Base Unit Conversion Adapter User's Manual