34
3 SPECIFICATIONS
3.3 Performance Specifications
NZ2GNCF1-32D DC input module
*1 The performance specifications vary depending on firmware versions of modules used. ( Page 256 Added and Changed Functions)
*2 If the input response time is set to "0ms", the actual input response time is 80s at OFF ON, and 160s at ON OFF.
*3 It is the noise immunity of when the input response time setting value is other than "0ms". Note that the module is easily affected by
noise if "0ms" is set.
*4 Use bar solderless terminals for wiring.
*5 Only one wire can be inserted into a wire insertion opening for the terminal block for module power supply and FG. Multiple wires cannot
be connected to a terminal. Connecting two or more wires may cause a poor contact.
*6 This value indicates the number of points set by default when the module is dragged and dropped to the network map in the CC-Link IE
TSN Configuration window. According to the function used, set an appropriate number of points. ( Page 225 Input module (32-point
module))
*7 For the points for downward installation, horizontal installation (upside down), and upward installation, refer to the derating chart below.
Item NZ2GNCF1-32D
Station type Remote station
Authentication Class Authentication Class B
Network topology Line topology, star topology, mixture of star topology and line topology, ring topology
*1
Number of input points 32 points
Rated input voltage 24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Rated input current 6.6mA TYP. (for 24VDC)
Maximum number of simultaneous input points 100%
*7
ON voltage/ON current 11VDC or more/4mA or more
OFF voltage/OFF current 5VDC or less/1.5mA or less
Input resistance 3.3k
Input response time OFF ON 0ms
*2
/0.2ms/1ms/1.5ms/5ms/10ms/20ms/70ms
(Factory default: 1ms)
ON OFF
Withstand voltage 510VAC for 1 minute between all DC external terminals and ground
Insulation resistance 10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise immunity
*3
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
Protection degree IP2X
Wiring method for common 32 points/common (Common terminal: pin number B1, B2) (1-wire, 40-pin connector type)
Positive common/negative common shared type
External interface Communication part RJ45 connector
Module power supply part Terminal block for module power supply and FG (2-piece spring clamp terminal block)
I/O part 40-pin connector
Applicable wire size For power supply Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.4mm 1.5mm
*4
For I/O 40-pin connector
The size depends on the connector plug used (sold separately). ( Page 141 Wiring of 40-pin
connector)
Applicable solderless
terminal
*5
Terminal block for module
power supply and FG
Page 127 Applicable solderless terminal
Multicast filter Available
*1
Cyclic transmission RX/RY points 32 points
RWr/RWw points 4 points
*6
Module power supply Voltage 24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current 110mA or less (24VDC, all points ON)
Weight 0.20kg
0
24
32
16
8
0 102030405055
28.8VDC
26.4VDC
Maximum
number of
simultaneous
ON points
(points)
Ambient temperature ()
28 points, 55
32 points, 55
32 points, 45
Input voltage
Input voltage

Table of Contents