11 TROUBLESHOOTING
11.4 Examples of Troubles with the I/O Module
115
11
When output is turned on, load connected to other outputs is turned on simultaneously
■Cause
When a non-wiring state occurs due to, for example, a shutoff or disconnection between 0V of the external power supply and
the common of a load, a current flows across the load that is off through an unexpected circuit of the output element that is off.
Continuous use in this state may cause failure.
■Action
Connect the external power supply with the load correctly.
To prevent the state described above, install diodes in each output terminal as shown below.
A load inputs data incorrectly due to a chattering.
■Cause
A device with a high input response speed is connected to the contact output module.
■Action
Use a transistor output module.