11 TROUBLESHOOTING
11.4 Examples of Troubles with the I/O Module
115
11
When output is turned on, load connected to other outputs is turned on simultaneously
Cause
When a non-wiring state occurs due to, for example, a shutoff or disconnection between 0V of the external power supply and
the common of a load, a current flows across the load that is off through an unexpected circuit of the output element that is off.
Continuous use in this state may cause failure.
Action
Connect the external power supply with the load correctly.
To prevent the state described above, install diodes in each output terminal as shown below.
A load inputs data incorrectly due to a chattering.
Cause
A device with a high input response speed is connected to the contact output module.
Action
Use a transistor output module.
ON
OFF
Y0
Y1
COM+
CTL-
Load
Load
24VDC
Shutoff or disconnection
Source output
Output control
circuit
Output control
circuit
Output module
Y0
Y1
COM+
CTL-
Load
Load
24VDC
Source output