76
6 INSTALLATION AND WIRING
6.2 Setting Switch
Function setting switch setting
Set the input response time setting and output HOLD/CLEAR setting using the function setting switch on the front of I/O
module.
Do not change the function setting switch while the module is powered on. Changing the function setting
switch while the module is powered on causes a minor error and flashes the ERR. LED. Returning the
function setting switch to the previous setting eliminates the error and turns off the ERR. LED.
No. Switch name Function to be used Setting details
1 Function setting switch 1 to 3 Input response time setting
function
Set the input response time.
For setting method, refer to the following.
Page 90 Setting method
2
3
4 Function setting switch 4 Output HOLD/CLEAR setting
function
Set output HOLD/CLEAR.
For setting method, refer to the following.
Page 91 Setting method