Appendix 5 Processing Time
131
A
Appendix 5 Processing Time
For the processing time of CC-Link IE Field Network Basic, refer to the following.
CC-Link IE Field Network Basic Reference Manual
Response processing time of slave station
This section shows the response processing time of slave station.
Input reflection processing time of slave station (input)
The input reflection processing time of the slave station (input) = Input response time
*1
+ Internal processing time (0.2ms)
*1 If the input response time is "0ms", use 0.14ms for calculation.
Output reflection processing time of slave station (output)
The output reflection processing time of the slave station (output) = Output response time (1.5ms at ON OFF) + Internal
processing time (0.2ms) = 1.7ms