3 SPECIFICATIONS
3.2 Performance Specifications
55
3
*1 If the input response time is set to "0ms", the actual input response time is 80s at OFF ON, and 160s at ON OFF.
*2 It is the noise immunity of when the input response time setting value is other than "0ms". Note that the module is easily affected by
noise if "0ms" is set.
*3 Only one wire can be connected to a terminal of the terminal block for module power supply and FG. Multiple wires cannot be connected
to a terminal. Connecting two or more wires may cause a poor contact.
*4 It is recommended to use the bar solderless terminal for wiring.
Reference response time 1ms
Communication cable An Ethernet cable that meets the 100BASE-TX standard
For details, refer to the following.
CC-Link IE Field Network Basic Reference Manual
Module power supply Voltage 24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current 79mA or less (24VDC, all points ON)
Weight 0.30kg
Item NZ2MFB1-32DTE1
Input specifications Output specifications