App - 8 App - 8
MELSEC-Q
APPENDICES
Appendix 2.2 G(P).OGLOAD
Reads the offset/gain values of the user range setting of the D/A converter module to
the CPU.
Setting
data
Usable devices
Internal device
(System, user)
File
register
Link direct device
J\
Intelligent
function module
device U \G
Index
register Z
Constant
Others
Bit Word Bit Word K, H $
(S) —
— — — —
(D)
— — — —
Setting data
Setting
data
Description Setting range Data type
Un Start I/O number of the module 0 to FEH Binary 16 bits
(S) Start number of the device in which control data is stored.
Within the range of the
specified device
Device name
(D)
Device that is turned on 1 scan on completion of dedicated
instruction processing.
(D) + 1 also turns on at an abnormal completion.
Within the range of the
specified device
Bit
Control data
1
of the Q62DAN and Q62DA
Device Item Setting data Setting range Set by
(S) System area — — —
(S) + 1 Completion status
Stores the status when the instruction
is complete.
0 : Normal completion
Other than 0 : Abnormal completion
— System
(S) + 2 Pass data classification setting
Specify the voltage/current of the
offset/gain values to be read.
0: Voltage specified
1: Current specified
0000H to 0003 H User
(S) + 3 System area — — —
(S) + 4 CH1 Industrial shipment settings offset value — — System
(S) + 5 CH1 Industrial shipment settings gain value — — System
(S) + 6 CH2 Industrial shipment settings offset value — — System
(S) + 7 CH2 Industrial shipment settings gain value — — System
(S) + 8 CH1 User range settings offset value — — System
(S) + 9 CH1 User range settings gain value — — System
(S) + 10 CH2 User range settings offset value — — System
(S) + 11 CH2 User range settings gain value — — System
1 Set only Pass data classification setting (S)+2. If data is written to the area set by the system, the offset/gain values
will not be read properly.
Command
G.OGLOAD
Command
GP.OGLOAD
Un (S)
(D)
Un (S) (D)
[Instruction
symbol]
[Execution
condition]
G.OGLOAD
GP.OGLOAD
0
0 CH.2 CH.1
b15 b2b1b0