6 - 100
: Self-diagnostics is performed, : Self-diagnostics is not performed
(To the next page)
Table6.27 Self-diagnostics list (continued)
Diagnostics
Error
message
Diagnostic timing
CPU
module
status
LED status Basic
model
QCPU
High
Performance
model QCPU
Process
CPU
Redundant
CPU
RUN ERR.
Redun-
dant sys-
tem error
Both systems
file
consistency
error
Parameter-
valid drive
consistency
error
CPU MODE
DIFF.
Power-on/reset
Execution of the END
instruction
Mounting of tracking
cable
Stop Off Flashing
Tracking data
communicati
on error
TRK.TRAN
S. ERR.
Always Continue On On
Tracking
capacity
excess error
TRK.SIZE
ERROR
Execution of the END
instruction
Continue On On
Tracking
cable error or
tracking
transfer
hardware
failure
TRK.CABL
E ERR.
Power-on/reset Stop Off Flashing
Tracking
cable not
connected,
failure, or
tracking
transfer
hardware
failure
TRK.
DISCON-
NECT
Always Continue On On
Tracking
transfer initial
error
TRK.INIT.
ERROR
Power-on/reset Stop Off Flashing
System
switching
from standby
system to
control
system
*6
CONTROL
EXE.
Always Continue On Off
System
switching
from control
system to
standby
system
*6
STANDBY Always Continue On Off
System
switching
error
CAN'T
SWITCH
System switching Continue On On
Standby
system not
started or
stop error
STANDBY
SYS.DOWN
Always Continue On On
Control
system not
started or
stop error
CONTROL
SYS.DOWN
Always Stop Off Flashing
Program
memory clear
PRG.MEM.
CLEAR
Execution of the program
memory copy function
Stop Off Flashing