E-36
FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
4 Wiring
4.8 Connection Diagram
3. When one inverter is connected (2-wire type)
4. When two or more (up to eight) inverters are connected (2-wire type)
When adopting branches, perform the wiring as shown below: (2-wire type)
Crossover
wiring
PLC
Inverter
Terminal resistor: 110 Ω
•
FX
3U
-485-BD, FX
3G
-485-BD, FX
3U
-485ADP(-MB):
Set the built-in selector switch.
0.3mm
2
or more
(0.3mm
2
or more)
Twisted pair cable
Ω
Set the terminal resistor switch to the
"100 " side.
Terminal
arrangement
Terminal
block
Connect them to PLC
communication unit.
Crossover
wiring
Crossover
wiring
Crossover
wiring
PLC
Inverter Inverter Inverter
Terminal resistor: 110 Ω
Ω
•
FX
3U
-485-BD, FX
3G
-485-BD, FX
3U
-485ADP(-MB):
Set the built-in selector switch.
For the pin arrangement of the connector,
refer to the connection diagram above for one inverter.
0.3mm
2
or
more
(0.3mm
2
or
more)
Twisted pair cable
Class D
grounding
Class D
grounding
Set the terminal resistor switch
to "100 " in the inverter located
furthest away from the PLC.
To PLC
To next station inverter
Perform crossover wiring.
For crossover wiring of a shielded cable using the terminal SG,
set the terminal 2/SG selector switch to the right side (ON) to
change over the terminal 2 to the terminal SG.
(By this setting, analog inputs to the terminal 2 become invalid.)
When connecting a 100 terminal resistor,
set the switch to the "100 " side.
Ω