22 - 43
22. TROUBLE SHOOTING
6210
[CONTROL WAIT ]
The control system in a redundant system is
switched to the standby system.
(This can be detected from the standby system of
the redundant system.)
â– Collateral informationmmon
• Common Information:Reason(s) for system
switching
• Individual Information:–
â– Diagnostic Timing
• Always
Check the control system condition.
RUN:
On
ERR.:
Off
CPU Status:
Continue
Q4AR
6220
[CAN'T EXE. CHANGE]
• Since the standby system is in an error or similar
status in the redundant system, the control
system cannot be switched to the standby
system.
• When an attempt was made to execute system
switching, the control system could not be
switched to the standby system due to a network
error of the control system.
(This can be detected from the control system of
the redundant system.)
â– Collateral informationmmon
• Common Information:Reason(s) for system
switching
• Individual Information:–
â– Diagnostic Timing
• At switching request
Check the standby system condition.
RUN:
On
ERR.:
On
CPU Status:
Continue
6221
[CAN'T EXE. CHANGE]
Switching is disabled because of a bus switching
module error.
(This can be detected from the control system of
the redundant system.)
â– Collateral informationmmon
• Common Information:Reason(s) for system
switching
• Individual Information:–
â– Diagnostic Timing
• At switching request
This is a bus switching module hardware fault.
(Contact your local Mitsubishi representative.)
6230
[DUAL SYS. ERROR]
The link module mounted on the standby system
CPU module is the remote master station.
â– Collateral informationmmon
• Common Information:–
• Individual Information:–
â– Diagnostic Timing
• Always
Check the system configuration status.
Error
Code
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU