App - 120
APPENDICES
Appendix 4.3 Parameters
The following parameter settings only are converted to QnACPU use.
• Latch range setting
Converted to the "latch clear key valid" range.
The latch clear key invalid range is made blank (no setting).
• MELSECNET (II, /10) setting
For the MELSECNET setting when the ACPU is an AnN or AnA, the number of
modules are stored after conversion, but the network refresh parameters are not
converted.
• I/O assignment
Only the head I/O No. is made blank; all other items are converted.
• MELSECNET/MINI auto refresh setting
If only I/O assignment was set in the parameters and MELSECNET/MINI auto refresh
settings have not been made, the MELSECNET/MINI data link operates with the
default values.
The following items are set for the QnACPU default.If settings have been made, make the
settings again.
• RUN-PAUSE contacts : No setting
• Output at STOP RUN : Before operation
• Interrupt counter No. : No setting
• WDT setting : 200ms
• Operation mode when
there is an error : STOP (All items)