7. AUTO REFRESH FUNCTION
* Only when the file register is set to "Use the designated file" with the "Parameter",
R and ZR can be used as the auto refresh devices. When "Use same file name as program" is
set, R and ZR cannot be used.
REMARK
Table 7.1 List of auto refresh settings (Continued)
Item Description Setting range
Setting station
MLT
Batch refresh device for
special register
The destination device for special register is set.
T, ST, C, D, W, R, ZR
*
Auto update buffer
specification
The buffer capacity for automatic update is set. 128 to 4096
Total number of slave
stations
The last station number of the remote station connected to the master station
is set.
1 to 64
Delay timer The delay time of link scan is set.
1 to 100
(0 is invalid.)
Standby station specification The use status of the stand-by master function is set.
Not used
Used
Number of retries The number of retries at the occurrence of a transient transmission error is set. 1 to 7
Number of automatic return
stations
The number of automatic return stations is set to one link scan. 1 to 10
Operation specification for
CPU stop
When the CPU module has stopped, continuation/stop of the data link is set.
•Stop
Continue
Scan mode setting Synchronization/Non-synchronization is set to the CPU module scan.
Non-synchronization
Synchronization
Station type The model for each remote station is set.
Remote I/O station
Remote device
station
Intelligent device
station
Number of occupied stations The number of occupied stations for each remote station is set.
1 station
•2 stations
•3 stations
•4 stations
Specification of reserved
station
Reservation for remote station is set.
•Not reserved
Reserved
Specification of invalid
station
Validity/Invalidity for error detection of the remote station is set.
•Invalid
Valid
1) In "Setting station" in the table above, M refers to the master station, L to the
local station, and T to the stand-by station.
2)
In the table above, means that the setting can be made and means that
the setting is not required.