© MOBATIME 84 / 120 800652.11
9.2 Device configuration with SNMP
If one or several variables are set with Put in a configuration group, the variable
dts480x????ConfigCmd must be set at the end to 1 in the corresponding group. The
values of the entire configuration group are assumed from the DTS with this command
(1=accept).
As long as the accept command has not been set, the changed variables can be
restored to the old values by setting the
dts480x????ConfigCmd variable to 2
(2=undo, restore).
After sending the accept command, a dts480xConfigChanged Notification is sent.
The definitions of the available variables can be taken from the MIB files and from the
menu descriptions of this manual.
Example:
Management System DTS
Put dts480xFTPMode=1 Variable is set to 1 internally
Put dts480xNetServicesConfigCmd=1 Configuration group is assumed
Sends dts480xConfigChanged Notification
with the new time
dts480xNetConfigChangedTime
9.3 DTS Subagent SNMP Notification
Protocol: SNMPv2c Notification
Important:
For Notifications to be sent out, SNMP must be switched on. In addition,
at least one receiver system must be configured.
9.3.1 Startup [dts480xStartUp]
Sent out when the subagent for the DTS is started.
This Notification is always sent out, as soon as SNMP is activated and a destination
address is configured.
9.3.2 Shutdown [dts480xShutdown]
Sent out when the subagent for the DTS is stopped.
This Notification is always sent out, as soon as SNMP is activated and a destination
address is configured.