EMC INDUSTRIAL GROUP LTD Connections
MW94A_IM_ALL_SV6.09f_en 11/53
disable START key
Key
Run/Stop/Pause Logic
The following table describes how the status is affected by the inputs.
Inputs (Control1) Outputs (Status1)
stop run pause start running paused run motor
1 X X X 0 0 0
0 1 0 X 1 0 1
0 0 0
0 *
0 0 0
0 X 1 X NC 1 0
0 0 0
1 0 1
0 0 1
1 1 0
KEY
Entry Description
0 input or output off
1 input or output on
X don’t care (either on or off)
NC no change
rising edge (input turns on)
*
remains off since last stop
Connection Principles
ModWeigh instruments can be configured in many different ways to suit any given application.
The display is normally located to suit an operator. The transmitter can be located in the field to reduce
field wiring or can be located with the display for a more conventional approach.
The I/O can conveniently be situated on a DIN rail in a cabinet.
ModWeigh digital output
+
AOx
ModWeigh digital input
ModWeigh analog output
[OUTx,
output function
]
[INx, input function]
pause/stop [INx, 31]
motor contactor (mc)
0V
run motor [OUT3, 56]
+24V
START
batch start [INx, 29]
PAUSE/STOP
paused [OUTx, 58]
PAUSED