EMC INDUSTRIAL GROUP LTD Outputs
MW94A_IM_ALL_SV6.09f_en 36/53
Outputs
Basic Settings
Inputs Internal Signals Outputs
Communications & Display
Information, Resets & Final Calibration
Analog output 1 (flowrate)
These variables select which signal should appear on the analog output and how it is to be scaled.
The speed demand varies from 0 to 100 % where 0 % means stopped and 100 % means maximum
speed. This demand is converted to an analog signal for connection to the motor speed controller. As
an example, a speed demand ranging from 0 to 100 % is to be converted to an analog signal ranging
from 4 to 20 mA.
Q2411 AO1 source (modbus address of signal) 8520, g10 flowrate=8762
Set this to the address of the transmitter’s signal that will be output via AO1.
Q2412 AO1 signal low 8522 0 FU
This is the low point of the signal to corresponding to the ‘AO1 current low’ setting (typically set to 0).
Q2413 AO1 signal high 8524 FCAP FU
This is the high point of the signal corresponding to the ‘AO1 current high’ setting (typically set to the
capacity of the signal).
Q2414 AO1 current low 8526, g10 4.000 mA
This is the low point of the analog output signal within the range 0 to 20 mA (typically set to 4mA).
Q2415 AO1 current high 8528, g10 20.000 mA
This is the high point of the analog output signal within the range 0 to 20 mA (typically set to 20mA).
Q2416 AO1 current (can override output signal) 8800, g10 mA
Displays AO1 current. This setting may be altered to temporarily manually set the output current. This
is useful to test the analog output. The output will return to normal after you exit from the settings.
Q2417 AO1 signal (can override output signal) 8804 FU
Displays the signal currently being output. If this value is altered, the output is set to a value corre-
sponding to the signal. This is useful to test the analog output. The output will return to normal after
you exit from the settings.
Analog output 2 (weight)
These variables select which signal should appear on the analog output and how it is to be scaled.
Q2421 AO2 source (modbus address of signal) 8530, g10 weight=8740
Set this to the address of the transmitter’s signal that will be output via AO2.
Q2422
AO2 signal low
8532 0 WU
This is the low point of the signal corresponding to the ‘AO2 current low’ setting (typically set to 0).
Q2423 AO2 signal high 8534 WCAP WU
This is the high point of the signal corresponding to the ‘AO2 current high’ setting (typically set to the
capacity of the signal).
Q2424 AO2 current low 8536, g10 4.000 mA
This is the low point of the analog output signal within the range 0 to 20 mA (typically set to 4mA).
Q2425 AO2 current high 8538, g10 20.000 mA
This is the high point of the analog output signal within the range 0 to 20 mA (typically set to 20mA).
Q2426 AO2 current (can override output signal) 8802, g10 mA
Displays AO2 current. This setting may be altered to temporarily manually set the output current. This
is useful to test the analog output. The output will return to normal after you exit from the settings.
Q2427 AO2 signal (can override output signal) 8806 WU
Displays the signal currently being output. If this value is altered, the output is set to a value corre-
sponding to the signal. This is useful to test the analog output. The output will return to normal after
you exit from the settings.