Appendix
05/06 AWB2724-1584GB
70
CAN(open)/easy-NET
Data transfer rate Kbit/s 10, 20, 50, 100, 125, 250, 500
Default: 125
Potential isolation from inputs/outputs/power supply Yes
Bus termination resistor EASY-NT-R plug (incl. bus terminating resistor 120 O)
Terminations 2 x RJ45, 8pole
CANopen operating mode
Station Number max. 126
PDO type
asynchronous,cyclical, acyclical
Device profile
to DS301V4
Power supply
Rated voltage
Rated value V DC, (%) 24, ( –15, +20)
Permissible range V DC
20.4 to 28.8
Residual ripple %
F 5
Input current at 24 V DC, typical mA
140
Voltage dips, IEC/EN 61131-2 m
10
Power loss at 24 V DC, typical W
3,4
Inputs
Digital inputs
Number 12
Inputs that can be used for analog signals
I 7,8,11,12
Inputs that can be used for pulse signals
(High-speed counters)
I 1,2,3,4
Inputs for interrupt generation I 1,2,3,4
Status indication
LCD display
Electrical isolation
from the power supply, PC interface No
Between each other
No
from the outputs, to CAN interfaces
Yes
Rated voltage
Rated value V DC 24
On “0” signal
I1 to I6 and I9 to I10 V DC < 5
I7, I8, I11, I12 V DC
< 8
On “1” signal
I1 to I6 and I9 to I10 V DC > 15
I7, I8, I11, I12 V DC > 8
Input current on “1” signal (at 24 V DC)
I1 to I6, I9 to I10 mA 3,3
I7, I8, I11, I12 mA 2,2