05/06 AWB2724-1584GB
Technical data
71
Delay time for “0” to “1”
I1 to I4 m 0,02
I5 to I12 m 0,25
Delay time for “1” to “0”
I1 to I4 m 0,02
I5 to I12 m 0,25
Cable length (unshielded) m 100
Additional input functions
Inputs for analog signals
Number 8 (I7, I8, I11, I12)
Signal range V DC
0 bis 10
Resolution analog V
0,01
Resolution digital Bit
10
Value
0 bis 1023
Input impedance kO
11,2
Accuracy of actual value
Two devices % g 3
Within a single device %
g 2
Input current mA
< 1
Cable length (shielded) m
30
Inputs for high-speed counters
I 1, I2
Number/value range Bit
2 x 16 bits (I1,I2)
1 x 32 bit (I1)
Max. frequency kHz
50
Count direction selectable via software
incrementing/decrementing
Cable length (shielded) m
20
Pulse shape
Square
Mark-to-space ratio
1:1
Incremental counter
I1, I2, I3, I4
Number 1
Value range Bit
32 Bit
Max. frequency kHz
40
Cable length (shielded) m
20
Pulse shape
Square
Counter inputs
I1,I2 = Counter input
I3 = Reference pulse
I4 = Reference window
Signal offset
90°
Mark to space ratio
1:1
Inputs for interrupt generation I1, I2, I3, I4
Max. frequency kHz 3