I.5 EC REQUIREMENTS
Cautionary Marking. See previous page.
Protection against electric shock. Electronic Equipment intended for installation in
closed electrical operating areas kept locked. Where Electronic Equipment requires
manual intervention, 412.2.1 of HD 384.4.41 S2 shall be consulted.
Fixed connection for protection. The equipment may have a continuous leakage
current of more than A.C. 3.5 mA or D.C. 10 mA in normal use and a fixed ground
connection is required for protection.
RCD. When the protection in installations with regard to indirect contact is achieved by
means of an RCD, their appropriate function/combination shall be verified. In any case
only a residual-current-operated protective device (RCD) of Type B is allowed. In fact a
D.C component can occur in the fault current in the event of a fault connection to earth.
Climatic Conditions. Equipment intended to operate within its performance specification
over the range of Class 3K3, as defined in table 1 of EN 60721-3-1, EN 60721-3-2, EN
60721-3-3, EN 60721-3-4, partly modified.
Pollution Degree 2 Installation. The equipment shall be placed in a pollution degree 2
environment, where normally only non-conductive pollution occurs. Occasionally,
however, a temporary conductivity caused by condensation is to be expected, when the
electronic equipment is out of operation.
EMC Requirements. The installer of the equipment is responsible for ensuring
compliance with the EMC standards that apply where the equipment is to be used.
Product conformity is subjected to filters installation and to recommended procedures, as
from section 3 of this manual.
Second Environment (EMC). Equipment intended to be connected to an industrial low-
voltage power supply network, or public network that does not supply buildings used for
domestic purposes (second environment, according to EMC Standards). It is not intended
to be used on a low-voltage public network that supplies domestic premises (first
environment). Radio frequency interference is expected if used on such a network.
Recovery Resistor Cable. Shielding of the recovery resistor cable, provided in kit for test
purposes, is recommended for ensuring compliance with the EMC standards.
Large-Scale Stationary Industrial Tools (WEEE, RoHS). Equipment intended for
installation as part of large-scale stationary industrial tools, covered by the exception of
Annex IA, No.6, of the European Directives 2002/96/EC (WEEE) and 2002/95/EC
(RoHS).