ioLogik E1200 Series Initial Setup
2-12
ATTENTION
Determine the maximum possible current for each power wire and common wire according
to its size and
maximum
allowable current spec. If the current exceeds the maximum rating, the wiring may overheat,
causing serious damage to your equipment. For safety reasons, we recommend an average cable size of 22
AWG. However, depending on the current load, you may want to adjust your cable size (the maximum wire size
for power connectors is 2 mm).
The power terminal block is located on the top panel of the unit. Connect the unit to a 12 to 36 VDC power
source as shown below.
Item Suggested Setting
Wire range 12 to 24 AWG
Screw Torque 7 lb-inch
Top View
If power is properly supplied, the Power LED will glow a solid amber color. Continue to configure the software
after you have finished installing the hardware.