ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-8
System
Parameter Name Description Start
Address
(decimal)
Point
Type
Start
Register
(decimal)
Length Access Type
deviceName Each byte
represents
ASCII code of
each character
5040 04:INPUT
REGISTER
35041 30 R word
deviceUpTime unit: sec(s) 5020 04:INPUT
REGISTER
35021 2 R word
firmwareVersion e.g. V1.2.3 ->
1st byte: 1,
2nd byte: 2,
3rd byte: 3
5029 04:INPUT
REGISTER
35030 2 R word
firmwareBuildDate e.g.
Build1605171
8 -->
16051718
5031 04:INPUT
REGISTER
35032 2 R word
lanIp e.g.
192.168.127.
254 -> 1st
byte: 192, 2nd
byte: 168, 3rd
byte: 127, 4th
byte: 254
5027 04:INPUT
REGISTER
35028 2 R word
lanMac e.g.
00:90:E8:3E:
18:CC -> 1st
byte: 0, 2nd
byte: 144, 3rd
byte: 232, 4th
byte: 62, 5th
byte: 24, 6th
byte: 204
5024 04:INPUT
REGISTER
35025 3 R word
modelName Each byte
represents
ASCII code of
each character
5000 04:INPUT
REGISTER
35001 10 R word
watchdogAlarmFlag 1: clear
watchdog
alarm
4144 01:COIL
STATUS
04145 1 R/W bit

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Moxa Technologies ioLogik E1214-T and is the answer not in the manual?

Moxa Technologies ioLogik E1214-T Specifications

General IconGeneral
BrandMoxa Technologies
ModelioLogik E1214-T
CategoryI/O Systems
LanguageEnglish

Related product manuals