9 Operation
Maschinenfabrik Reinhausen GmbH 2021 1077817454/02 EN TAPCON
®
230 Expert
Setting Behavior
Auto/manual blocking The Reversal of power flow event is issued.
If Z compensation is activated, this function is deacti-
vated.
Automatic regulation is blocked.
You cannot perform tap-change operations in manual
mode.
Target tap position The Reversal of power flow event is issued.
If Z compensation is activated, this function is deacti-
vated.
The device triggers a tap-change operation to the tap
position you defined in the "Target tap position" pa-
rameter.
The device blocks further tap-change operations.
The target-tap-position operation is ignored if there is
no tap-position capture. Automatic regulation is
blocked.
Table40: Behavior in the event of a reversal of power flow
9.2.6 TAPCON® 2xx retrofit
The TAPCON® 2xx retrofit function allows you to operate the device in par-
allel operation with existing devices. Parallel operation with the following ex-
isting devices is supported:
Predecessor devices: TAPCON®230 pro/expert
TAPCON®240
TAPCON®250
TAPCON®260
TRAFOGUARD® with "Voltage regulation" options package
If you wish to operate several devices in parallel operation with existing de-
vices, you have to activate the TAPCON®2xx retrofit function on each de-
vice.
Figure47: Parallel operation of 2 devices with one TAPCON® 2xx