6 Mounting
Maschinenfabrik Reinhausen GmbH 202136 7817454/02 ENTAPCON
®
230 Expert
6.2 Minimum distances
NOTICE
Damage to the device!
Insufficient circulation of ambient air can result in damage to the device due
to overheating.
► Keep the ventilation slots clear.
► Ensure sufficient distance to neighboring components.
► Only mount device in horizontal position (ventilation slots are at the top
and bottom).
To the base of the control cabinet Minimum clearance: 88.9mm (3.5in)
Equivalent to 2RU
To the roof of the control cabinet
Between the device and other assem-
blies on offset cap rails
Table9: Minimum clearances in the control cabinet
88.9mm (3.5in)
88.9mm (3.5in)
Figure16: Minimum clearances
For other installation types, contact Maschinenfabrik Reinhausen GmbH.
6.3 Assembly variants
6.3.1 Flush panel mounting
The device can be mounted in a control panel using tension clamps. The
recommended wall thickness is 2...5mm.