3 IT security
Maschinenfabrik Reinhausen GmbH 2021 177817454/02 EN TAPCON
®
230 Expert
3.4 Communication interfaces
1
2
3
4
5
6
X1
RY
SICAM A8000
CP - 8050
ER
X2
X3
X4
X5
ETH
ETH
RS-485
RS-232
Figure1: Interfaces: CPU
Interface Protocol Port Description
X2 TCP 102 IEC61850
X2 TCP 502 Modbus
1)
X2 TCP 20000 DNP3
1)
X2 TCP 2404 IEC 60870-5-104 1)
X3 TCP 80 HTTP for web-based visualization
2)
X3 TCP 443 HTTPS for web-based visualization
X3 TCP 22 SSH server
3)
X4 - - Serial interface (SCADA)
X5 - - Serial interface (SCADA)
Table5: Interfaces and open ports of the CPU assembly
1)
Default setting; if you have modified the port for the control system proto-
col, only the set port is open.
2)
Port is closed if you activate the device's SSL encryption.
3)
SSH is disabled when MR service access is disabled.