EasyManua.ls Logo

MSA FL500 - Specifications; System Specifications

MSA FL500
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36
Specifications
FL500 UV/IR Flame Detector
US
8 Specifications
8.1 System Specifications
* Applicable to FM approvals only.
Notes:
Response times and field of view data were derived by testing the device with a 1 ft
2
heptane fire. One
cup of heptane on top of a 1-in. layer of water was ignited for each test. These are typical values. The
variation of each fire can cause different results.
BS EN 54-10 identifies the limit of the field of view to ±25 degrees because of the requirements of the
Directional Dependence test. This result is from indoor benchtop testing with a Bunsen burner as the
fire source, rather than the outdoor flame testing used to identify the field of view in Section 3.2.1
"Field of View".
Application
UV/IR Flame
Detection
Device location
Class I, Division 1, Groups A*, B, C, and D
Class II, Division 1, Groups E, F, and G
Class III
Ex db IIC T5 Gb
Ex tb IIIC T100°C Db
II 2 G D
-50°C to 85°C under FM, -55°C to 85°C under
CSA/ATEX/IECEx
Environmental ratings Type 6P, IP66/IP67
UV Detector pass band 185 - 260 nanometers
IR Detector center wave-
length
4.35 mm
Typical alarm activation
response times
Fuel Distance (ft)
Response Time
(s)
n-Heptane
90
60
6
<3
Methane 80 <10
Methanol 40 12
Propane 60 <7
Ethane 60 <3
Butane 55 <3
Zeta value
Zeta = -0.001
The margin of error in the range measurement is esti-
mated at ±5 ft (±1.5 m) due to wind conditions and flame
turbulence.
Field of view Refer to Section 3.2.1 "Field of View" for information.

Related product manuals