EasyManua.ls Logo

MSA FL500 - Environmental Specifications

MSA FL500
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38
Specifications
FL500 UV/IR Flame Detector
US
8.4 Environmental Specifications
RFI/EMI protection Complies with BS EN 50130-4 and BS EN 61000-6-4
Status indicator Three LEDs identify status, fault, and alarm conditions
Operating temperature
range
-67°F to 185°F (-55°C to 85°C)
Storage temperature range -40°F to 185°F (-40°C to 85°C)
Humidity range 0% to 95% RH noncondensing
False Alarm Source Distance from FL500 (ft) Trouble / False Alarm
Direct sunlight 3N
Reflected sunlight 3N
Arc weld dc 190A,
7014 rod
15 N
Arc weld ac 90A, 7014 rod 15 N
1500W electrical heater 2N
6000W electrical heater 2N
100W incandescent light 1N
300W incandescent light 1N
Two 34W fluorescent light 1N
500W halogen light 2N
100W UV backlight 3N
250W vapor lamp 3N
Two 25W tungsten incan-
descent lamps
3N

Related product manuals