PID SID FMI Description Maintenance tasks
13 111 4 Coolant level sensor, input
voltage too low.
1. Check coolant condition
(→ Page 119).
2. Check coolant level, top up if
required (→ Page 112).
3. Check cabling.
4. Contact Service.
13 111 6 Sensor "Top up coolant", in‐
put voltage too low.
1. Check coolant condition
(→ Page 119).
2. Check coolant level, top up if
required (→ Page 112).
3. Check cabling.
4. Contact Service.
14 52 3 Temperature sensor/inter‐
cooler, input voltage too
high.
1. Check cabling.
2. Contact Service.
14 110 3 Coolant temperature sen‐
sor, input voltage too high.
1. Check cabling.
2. Contact Service.
14 175 3 Oil temperature sensor, in‐
put voltage too high.
Contact Service.
15 52 4 Temperature sensor/inter‐
cooler, input voltage too
low.
1. Check cabling.
2. Contact Service.
15 110 4 Coolant temperature sen‐
sor, input voltage too low.
1. Check cabling.
2. Contact Service.
15 175 4 Oil temperature sensor, in‐
put voltage too low.
Contact Service.
16 111 3 Coolant level sensor, input
voltage too high.
1. Check coolant condition
(→ Page 119).
2. Check coolant level, top up if
required (→ Page 112).
3. Check cooler for dirt.
4. Check cabling.
5. Contact Service.
16 111 5 Sensor "Top up coolant", in‐
put voltage too high.
1. Check cabling.
2. Contact Service.
17 51 3 Throttle sensor, input volt‐
age too high.
1. Check cabling.
2. Contact Service.
17 72 3 Blower bypass position, in‐
put voltage too high.
1. Check cabling.
2. Contact Service.
17 354 3 Humidity sensor, electric
circuit defective / high (ver‐
sion 33.0 or later).
1. Check cabling.
2. Contact Service.
54 | Troubleshooting | MS150049/02E 2012-11