5.13 Emergency engine shutdown at LOP (without BlueLine
automation system)
NOTICE
An emergency stop causes extreme stress to the engine plant.
Risk of overheating, damage to components!
• Initiate emergency stop only in emergency situations.
Emergency engine shutdown from LOP
Item Action
LOP Open cap of illuminated pushbutton EMERGENCY STOP (→ Page 35).
LOP Press illuminated pushbutton EMERGENCY STOP.
• Engine is stopped by disconnecting the power supply to the ECU;
• On engines with emergency air-shutoff flaps: flaps close;
• Illuminated pushbutton EMERGENCY STOP flashes. Horn, flashing lamp
etc. are tripped.
After emergency engine shutdown from LOP
Item Action
LOP Press illuminated pushbutton ALARM ACKNOWLEDGE (→ Page 35).
• Audible and visual alarm signaling stops.
LOP Press illuminated pushbutton ALARM ACKNOWLEDGE again.
• Power supply to ECU is provided;
• Alarm has been acknowledged.
Engine On engines with emergency air-shutoff flaps: open flaps.
• Engine is ready for starting.
48 | Operation | MW15409/04E 2015-08
TIM-ID: 0000002313 - 004