© Munters AB, 2020 30
7.2.2
E
XTRA
V
ENTILATION
If enabled, Extra Ventilation acts as a transitional phase. Extra Ventilation operates in situations where:
•
Basic Ventilation does not provide enough air to lower the temperature to the Target
Temperature
•
The temperature is still below the Tunnel Set Point.
•
Trio only enters Extra Ventilation if the temperature is 0.5⁰ above the Target Temperature (this is
the minimum; you can set the differential to be higher).
•
You can set a differential for each level to ensure that ventilation increases only when required.
•
Extra Ventilation supports up to 10 levels. As in Basic Ventilation, you define the fans to be used
in each level. However, there is no curve between levels.
In the example below, Extra Ventilation is running at Level 15. The minimum for this growth day is Level 3
(30%) and the maximum is Level T1 (first tunnel level).
Refer to Extra Ventilation, page 53 for more details.