EasyManua.ls Logo

Murphy Selectronic TTD Series - Communications; Communications Port

Murphy Selectronic TTD Series
58 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 50 00-02-0329
01-09-07 - 42 -
Communications
Communications Port
A single bi-color (GREEN/RED) LED will be provided to give visual indication of active transmit
and receive traffic. Only one connection will be active at any time.
Interface: Factory configured for RS485; field-selectable for RS232 or RS485.
Baud/Configuration: 9600, 19.2K, 38.4K(*);N,8,1;N,8,2 (setup configuration is in SETUP 9)
Protocol: Modbus (Slave)
Connection: There will be 2 screw terminal connectors for RS485.
These will be printed or labeled as A and B.
There will be 2 screw terminal connectors for RS232.
These will be printed or labeled as RX and TX.
There will be 1 screw terminal common for both ports.
This will be printed or labeled as GND.
(*) 38.4K Baud will not be available when IGN input is selected as the source for RPM calculations. When MPU is selected,
this feature is available for selection.
To order call 1-800-548-1191 or visit www.partdeal.com - info@partdeal.com

Related product manuals