Section 50 00-02-0329
01-09-07 - 42 -
Communications
Communications Port
A single bi-color (GREEN/RED) LED will be provided to give visual indication of active transmit
and receive traffic. Only one connection will be active at any time.
Interface: Factory configured for RS485; field-selectable for RS232 or RS485.
Baud/Configuration: 9600, 19.2K, 38.4K(*);N,8,1;N,8,2 (setup configuration is in SETUP 9)
Protocol: Modbus (Slave)
Connection: There will be 2 screw terminal connectors for RS485.
These will be printed or labeled as A and B.
There will be 2 screw terminal connectors for RS232.
These will be printed or labeled as RX and TX.
There will be 1 screw terminal common for both ports.
This will be printed or labeled as GND.
(*) 38.4K Baud will not be available when IGN input is selected as the source for RPM calculations. When MPU is selected,
this feature is available for selection.