12
4.5 CIRCUIT PROTECTION
Buss Power
ThemoduleshallmonitorPowerBussBankcurrentandshutoallbankoutputsifthemaximumcurrentexceeds13ampsperbuss.
Bothshortcircuitandovercurrentprotectionisprovided.
P1=Ports1&2power,13amps.
P2=Ports3&4power,13amps.
Module Power
ThiscircuithasaseparategroundthatissuppliedbytheCANportaswell,Ground(A)
Output Power
Thismodulehas4ampoutputs.Theoutputshavebothshortcircuitandovercurrentprotection.(SeeFigure1)
(8)4Aoutputs
ResetinganoutputfaultwillrequirecyclingofthemodulepowerunlesstheControllerModeOutputResetisenabled.Ifthe
ControllerModeOutputResetisenabledthefaultwillberesetiftheoutputisturnedo,limitof5timesbeforeacycleofmodule
powerwillberequired.
Anoutputfaultwillnoteectotheroutputsonthemodule.
.01 .02 .03 .04 .05 .06
2
4
6
8
10
12
14
.00
Output Over Current Curve
Seconds
Amps
Figure1
Sec Amps
.00 12
.01 8
.02 6
.03 5.3
.04 4.8
.05 4.4