5. MODULE CONFIGURATION
Module default conguration:
•FactoryDefaultCongreturns1inStatusmessage1-Status1,thisshouldnotbeonifthemodulehasbeencongured.
•Defaultoperationofthemoduleison/odigitalcontrol.PWMcontrolmessagesarenotneeded.
•DefaultcongurationdoesnotrequireaCommand0x52hmessagetoenableoperation.
Command 0x52h (This message needs to be sent until the message conrmation bit is set true):
Value Name Data Type Byte Bits Description
82(0x52h) Command Byte 1 Commandforindexpointer(whichmessageyoursending)
CtrlModeReset
2 bit
2
1,2 EnablesControllerModeOutputReset
EnableStatus1Msg 3,4 Enablestheconstanttransmissionofstatusmessage1
EnableStatus2Msg 5,6 Enablestheconstanttransmissionofstatusmessage2
EnableAmpMsg 7,8 Enablestheconstanttransmissionofamperagemessages
Enable24vdc
3
1,2 Enablesthelowandovervoltagefaultlimitsfor24VDCsystem
SaveConguration 3,4
Savesthecongurationtothemodule(otherwisechangesonlyvaliduntilapowercycleoccurs),
setto1towritecongurationtomodule
Analograwvalue 5,6 Setsallanalogtobereadinrawvalueasopposedtoscaled(.005668/bit)
7,8
4
1,2
3,4
5,6
7,8
FREQ1 Word
5
Setstheglobalcongurationofthefrequencyforallchannels.
LowByteFREQ1:Valueindecimal(40-1100Hz).Example:0xC8h=200d=200Hz.
6 HighByteFREQ1
MODE1 4 Bit
7
SetstheglobalcongurationofALLtheoutputs,overides0x53hand0x54h.
0=Mode1NotUsed,1=ON/OFF,2=Data0-4000,3=Percent0-100.0%(0-1000),
(4=Amps(0-4000ma)Cannotbeusedinthismode.)
MODE2 4 Bit
Setstheglobalcongurationoftheinputs.
0=Mode2NotUsed,1=DigitalPositive,2=DigitalGround
(Noanalog3-7cannotbeusedinglobalcongurationmode)
ID1 Byte 8 UserdenedbyteforcongurationID,thiswillbetransimittedintheSTATmessage.
•Modulecongurationmessage,neededwhennotusingmoduledefaultconguration.
•AllStatusmessagesneedtobeturnedon(settovalueof1)tobereceived.
•Enable24VDC:Enablesthelowandovervoltagefaultlimitsfor24VDCsystem,otherwisefeeding24VDCto12VDCsystem
wouldcausesystemovervoltageerror.Thisisalsousedfortheoutputovercurrentandshortcircuitdetection.
•FREQ1:Thereneedstobeavalueputinthisparameterortheoutputswon’twork.
5.1 CONFIGURATION STEPS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Murr Elektronik Data Panel xtreme DB DP-34044-1 and is the answer not in the manual?

Murr Elektronik Data Panel xtreme DB DP-34044-1 Specifications

General IconGeneral
BrandMurr Elektronik
ModelData Panel xtreme DB DP-34044-1
CategoryControl Unit
LanguageEnglish

Related product manuals