Chapter 3 Configuring Your SCXI Hardware and Software
© National Instruments Corporation 3-47 Getting Started with SCXI
SCXI-1163R Module
The SCXI-1163R is an SCXI module consisting of 32 optically-isolated
solid-state relays. The SCXI-1163R module switches loads up to 240 V
rms
or VDC and 200 mA.
The SCXI-1163R operates in serial mode with MIO and AI devices,
Lab/1200 devices, and DIO devices. You can control several SCXI-1163R
modules in serial mode in a single chassis with one DAQ device.
Alternatively, you can control 24 of the solid-state relays in parallel mode
with a DIO-24, or all 32 solid-state relays in parallel mode with a DIO-32
or DIO-96/PnP.
Note
You should change the jumper configuration from the factory-default settings only
if you plan to connect the SCXI-1163R directly to an MIO and AI device, or if you plan to
use the SCXI-1163R in parallel mode.