There are two ways of activating connected accessories.
You can either mark the alternative in the list or use the
automatic function "search installed acc.".
search installed acc.
Mark “search installed acc." and press the OK button to
automatically find connected accessories for F1245.
Caution
"level sensor" are not found automatically but
must be ticked off by hand.
NOTE
Only mark the option for ground water pump
if the accessory AXC 40 is to be used to control
the circulation pump.
Menu 5.3 - accessory settings
The operating settings for accessories that are installed
and activated are made in the sub-menus for this.
Menu 5.3.1 - FLM
time between defrosts
Setting range: 1 – 30 h
Default value: 10 h
months btwn filter alarms
Setting range: 1 – 12
Default value: 3
continuous pump op.: Select for continuous operation
of the circulation pump in NIBE FLM.
time between defrosts: Set the minimum time that
must pass between defrostings of the heat exchanger in
NIBE FLM.
When the exhaust air module is in operation the heat
exchanger is cooled so that ice builds up on it. When too
much ice builds up the heat transfer capacity of the heat
exchanger is reduced and defrosting is required. Defrost-
ing warms up the heat exchanger so that the ice melts
and runs off via the condensation hose.
months btwn filter alarms: Set how many months
should pass before the heat pump informs that it is time
to clean the filter in NIBE FLM.
Clean NIBE FLM's air filter regularly, how often depends
on the amount of dust in the ventilation air.
Menu 5.3.2 - shunt controlled add. heat
start addition
Setting range: -2000 – -30 GM
Default values: -400 GM
minimum running time
Setting range: 0 – 48 h
Default value: 12 h
min temp.
Setting range: 5 – 90 °C
Default value: 55 °C
mixing valve amplifier
Setting range: 0.1 –10.0
Default value: 1.0
mixing valve step delay
Setting range: 10 – 300 s
Default values: 30 s
Set when the addition is to start, the minimum run time
and the minimum temperature for external addition with
shunt here. External addition with shunt is then for ex-
ample wood/oil/gas/pellet boiler.
For the shunt you can set shunt amplification and shunt
waiting time.
See the accessory installation instructions for function
description.
Menu 5.3.3 - extra climate system
mixing valve amplifier
Setting range: 0.1 –10.0
Default value: 1.0
mixing valve step delay
Setting range: 10 – 300 s
Default values: 30 s
Set the shunt amplification and shunt waiting time for
the different extra climate systems that are installed.
See the accessory installation instructions for function
description.
NIBE™ F1245Chapter 8 | Control - Menus64