EasyManuals Logo

Nibe F370 Installer Manual

Nibe F370
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #54 background imageLoading...
Page #54 background image
Menu 5 - SERVICE
Overview
5.1.1 - hot water settings5.1 - operating settings5 - SERVICE
5.1.2 - max flow line temperature
5.1.4 - alarm actions
5.1.5 - fan sp. exhaust air
5.1.12 - internal electrical addition
5.1.13 - max inst. el.pwr (BBR)
5.1.99 - other settings
5.2.4 - accessories5.2 - system settings
5.3.3 - extra climate system *5.3 - accessory settings
5.4 - soft in/outputs
5.5 - factory setting service
5.6 - forced control
5.7 - start guide
5.8 - quick start
5.9 - floor drying function
5.10 - change log
5.12 - country
* Accessory needed.
Go to the main menu and hold the Back button in for
7 seconds to access the Service menu.
Sub-menus
Menu SERVICE has orange text and is intended for
the advanced user. This menu has several sub-menus.
Status information for the relevant menu can be found
on the display to the right of the menus.
operating settings Operating settings for the heat
pump.
system settings System settings for the heat pump,
activating accessories etc.
accessory settings Operational settings for different
accessories.
soft in/outputs Setting software controlled in and
outputs on the input circuit board (AA3).
factory setting service Total reset of all settings (includ-
ing settings available to the user ) to default values.
forced control Forced control of the different compon-
ents in the heat pump.
start guide Manual start of the start guide which is
run the first time the heat pump is started.
quick start Quick starting the compressor.
NOTE
Incorrect settings in the service menus can
damage the heat pump.
Menu 5.1 - operating settings
Operating settings can be made for the heat pump in
the sub menus.
Menu 5.1.1 - hot water settings
economy
Setting range start temp. economy: 15 - 52 °C
Factory setting start temp. economy: 45 °C
Setting range stop temp. economy: 15 - 55 °C
Factory setting stop temp. economy: 51 °C
normal
Setting range start temp. normal: 15 - 52 °C
Factory setting start temp. normal: 49 °C
Setting range stop temp. normal: 15 - 55 °C
Factory setting stop temp. normal: 55 °C
luxury
Setting range start temp. lux: 15 - 62 °C
Factory setting start temp. lux: 52 °C
Setting range stop temp. lux: 15 - 65 °C
Factory setting stop temp. lux: 58 °C
stop temp. per. increase
Setting range: 55 70 °C
Factory setting: 60 °C
NIBE™ F370Chapter 8 | Control - Menus52

Other manuals for Nibe F370

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nibe F370 and is the answer not in the manual?

Nibe F370 Specifications

General IconGeneral
TypeExhaust Air Heat Pump
RefrigerantR290
Energy classA++
Energy Efficiency Class (Space Heating, 35°C)A++
Energy Efficiency Class (Space Heating, 55°C)A+
ApplicationResidential
Hot Water Tank Volume170 l
Heating Power8.5 kW

Related product manuals