Service menus
FIGHTER 1120
54
Operating settings
Menu 9.2.5 System 2 Present
This menu is used to select “On” or “Off” depending on
whether you have shunt group 2 (accessory ESV 20
needed).
Off
System 2 Present
9.2.5
Menu 9.2.6 Room disp Present
No function
Off
Room disp Present
9.2.6
S
S
Menu 9.2.7 Circ. pump 1
Here you set whether heat medium pump should run
constantly in “Summer mode”. The value is adjustable
“On” or “Off”. Changes to “Off” with a restart.
Off
Circ. pump 1
9.2.7
S
Menu 9.2.8 Circ. pump 2
Here you set whether heat medium pump 2 should run
constantly in “Summer mode”. The value is adjustable
“On” or “Off”. Changes to “Off” with a restart.
Off
Circ. pump 2
9.2.8
S
Menu 9.2.9.0 Floor drying set
Settings for the floor drying program are made in the
sub-menus to this menu.
Floor drying set
9.2.9.0
S
Menu 9.2.9.1 Floor drying
The floor drying program is chosen from this sub-
menu. The options are “Prog 1 On”, “Prog 2 On” or
“Off”. The heat pump must be in “Winter mode”,
selected with the operating mode button. Electric boil-
er mode, Menu 9.2.4 can be used together with floor
drying, for example, when the heat source is not
installed.
In “Prog 1 On”, menus 9.2.9.2 - 9.2.9.5 are shown.
After time period 1 a switch is made to time period 2
followed by a return to the normal settings.
In “Prog 2 On”, a fixed program over 11 days is fol-
lowed. The flow temperature is increased from 20 to
45 °C for 4 days, it then remains constant for 3 days.
The temperature then steps down to 25 °C for 4 days,
and then returns to the normal settings.
Off
Floor drying
9.2.9.1
Menu 9.2.9.2 Numb. of days per. 1
Selection of the number of days in period 1.
The value is adjustable between 1 and 5.
3
Numb. of days per. 1
9.2.9.2
Menu 9.2.9.3 Temp. period 1
Selection of the flow temperature in period 1.
The value is adjustable between 15 and 50 °C.
25°C
Temp. period 1
9.2.9.3
S
S
S
Menu 9.2.9.4 Numb. of days per. 2
Selection of the number of days in period 2.
The value is adjustable between 1 and 5.
1
Numb. of days per. 2
9.2.9.4
Menu 9.2.9.5 Temp. period 2
Selection of the flow temperature in period 2.
The value is adjustable between 15 and 50 °C.
40°C
Temp. period 2
9.2.9.5
S
S
Menu 9.2.4 Add heat only (el. boiler)
Only additional heat is activated when “On” is shown
on the display, otherwise “Off” is shown. When only
additional heat is activated, the immersion heater
respective circulation pump cannot be blocked with
the operating mode button. NOTE! Select “Off” to
deactivate only additional heat and select the
required operating mode using the operating
mode button.
Off
Add heat only
9.2.4
S