EasyManua.ls Logo

Nibe FIGHTER 1240 - Connecting the Outside Temperature Sensor; Alarm;Alarm Outputs; Soft-Start Relay

Nibe FIGHTER 1240
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical connection
23
FIGHTER 1240
Install the outside temperature sensor in the shade on
a wall facing north or north-west, so it is unaffected by
the morning sun. The sensor is connected to terminals
X1:1 and X1:2 on the EBV-card (2). Use a two-wire
cable of at least 0.5 mm
2
.
If the outside temperature sensor cable runs close to
power cables, screened cable should be used.
All conduits should be sealed to avoid condensation in
the sensor capsule.
Alarm
A common alarm is given in the following instances:
High pressure switch (HP) has tripped. Indicated as
HP alarm.
LP pressure switch (LP) has tripped. Indicated as an
LP alarm.
The motor cut-out (MP) has tripped, indicated by an
MP alarm.
Pressure/level monitor brine (accessory) indicated as
pressure/level brine.
Brine temp. low, indicates a low brine temperature. Not
indicated when menu 5.2 is set to automatic return On.
Flow sensor fault is indicated by a Sensor alarm.
Hot water sensor fault is indicated by a Sensor alarm.
External indication of common alarms is possible
through the relay function on the load monitor card (2),
terminals X2:1—3.
The picture shows the relay in the alarm position.
When switch (8) is in the 0 or “ ” position the
relay is in the alarm position.
Alarm/alarm outputs
Connecting the
outside temperature sensor
Outdoor temperature sensor
Alarm output,
common
alarm
FIGHTER 1240 is equipped with a soft-start relay (97),
which limits the inrush current, see section Technical
specifications.
The compressor must not be forced to start with peri-
ods shorter that 1 start per 15 minutes.
Soft-start relay*
*Applies to 3 x 400 V and 1 x 230 V -8 and -12
X2
LEK
2
X1

Table of Contents

Related product manuals