Service menus
FIGHTER 1240
46
Quick start
Menu 9.4.1.26 Return
Pressing the enter button returns you to menu 9.4.0.
Return
9.4.1.26
Menu 9.3 Quick start
When Yes is selected, the heat pump starts within 5
minutes. Returns automatically to No, which indicates
that quick start is activated.
No
Quick start
9.3
S
TEST Force driven operation
Menu 9.4.0 TEST/Forced operat.
Test of outputs, automatic return after 30 minutes.
Only for service personnel.
TEST/Forced operat.
9.4.0
S
Menu 9.4.1.0 Forced operation
Selectable between On or Off.
Off
Forced operation
9.4.1.0
S
Menu 9.4.1.1 — 9.4.1.25
Manual test of relays, opto and AD.
RE1
9.4.1.1
S
Menu 9.2.15 RCU Present
Here you select whether RCU is installed.
Off
RCU Present
9.2.15
S
Menu 9.2.14 Factory setting
Return to the factory settings in FIGHTER 1240, Yes
or No. When returning to the factory settings the lan-
guage switches to English.
No
Factory setting
9.2.14
S
Menu 9.2.16 Cooling system
Here you select whether HPAC, PKM, PKI or PK4 is
installed.
Off
Cooling system
9.2.16
S
Menu 9.2.17 TB-alarm activated
Here the temperature limiter alarm can be selected to
be activated or not.
Off
TB-alarm activated
9.2.17
S
Menu 9.2.18 Roomsensor type"
Type of room control to be activated can be selected
here. Options are “Off”, “RG05”, “RG10” and “RE10”.
Off
Roomsensor type
9.2.18
S
Operating settings
Menu 9.2.21 Return
Pressing the enter button returns you to menu 9.2.0
Return
9.2.21
Menu 9.2.20 Phase fault Alarm
Select here whether the phase sequence alarm is to
be active or not.
Note! Incorrect phase sequence can seriously dam-
age the compressor.
Off
Phase fault Alarm
9.2.20
S