EasyManua.ls Logo

Nibe FIGHTER 1240 - Page 47

Nibe FIGHTER 1240
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Service menus
45
FIGHTER 1240
Menu 9.2.9.1 Floor drying
The floor drying program is chosen from this sub-
menu. The options are Prog 1 On, Prog 2 On or Off
The heat pump must be in Winter mode, selected with
the operating mode button. Electric boiler mode, Menu
9.2.4 can be used together with floor drying, for exam-
ple, when the heat source is not installed.
In Prog 1 On, menus 9.2.9.2 — 9.2.9.5 are shown.
After time period 1 switching to time period 2 then
Return to normal settings.
In Prog 2 On, a fixed program over 11 days is fol-
lowed. The flow temperature is increased from 20°C
to 45°C for 4 days, it then remains constant for 3 days.
The temperature then steps down to 25°C for 4 days,
and then returns to the normal settings.
Off
Floor drying
9.2.9.1
Menu 9.2.9.2 Numb. of days per. 1
Selection of the number of days in period 1.
The value is adjustable between 1 to 5.
3
Numb. of days per. 1
9.2.9.2
Menu 9.2.9.3 Temp. period 1
Selection of the flow temperature in period 1.
The value is adjustable between 15 and 50 °C.
25°C
Temp. period 1
9.2.9.3
S
S
S
Menu 9.2.9.4 Numb. of days per. 2
Selection of the number of days in period 2.
The value is adjustable between 1 to 5.
1
Numb. of days per. 2
9.2.9.4
Menu 9.2.9.5 Temp. period 2
Selection of the flow temperature in period 2.
The value is adjustable between 15 and 50 °C.
40°C
Temp. period 2
9.2.9.5
S
S
Menu 9.2.10 Pool control
Settings whether pool control should be On or Off.
Basic setting is Off.
Off
Pool control
9.2.10
S
Operating settings
Menu 9.2.9.6 Return
Pressing the enter button returns you to menu 9.2.9.0
Return
9.2.9.6
S
Menu 9.2.11 Brine pressostat
You set here whether an external an brine presso-
stat/load monitor is connected to the load monitor
card.
Off
Brine pressostat
9.2.11
S
Menu 9.2.12 Oper. mode brinepump
The operating mode for the brine pump is set here.
Selectable options are:
Intermittent: The brine pump starts 20 seconds
before and stops 20 seconds after the compressor.
Continuous: Continuous operation.
10 days. cont: Continuous operation for 10 days.
Then the pump shifts to intermittent mode.
Intermittent
Oper. mode brinepump
9.2.12
S

Table of Contents

Related product manuals