EasyManua.ls Logo

Nibe VVM 310 - Page 17

Nibe VVM 310
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connecting to heat pump
All outdoor pipes must be thermally insulated with at
least 20mm thick pipe insulation.
VVM 310 is not equipped with shut off valves; these
must be installed outside the indoor module to facilit-
ate any future servicing.
NOTE
The charge circuit is supplied with trim valve
for basic setting of the charge flow.
-FL2
-CM1
-EB15
-XL8
-XL9
-RN10
-EB101
XL2
XL1
-HQ1
-QM1
-QM41
-FL10
-QM40
-EB101
Connection as electric boiler
Connect the pipe for docking in from the heat pump
(XL8) with the pipe out to the heat pump (XL9).
-FL2
-CM1
-EB15
-XL8 -XL9
Connecting cold and hot water
The mixing valve must be installed if the factory setting
is changed so that the temperature can exceed 60 °C.
If the factory setting is changed, national regulations
must be observed. The setting is made in menu 5.1.1
(See page 51).
-FL2
-XL4
-XL3
-CM1
-EB15
-FL1
-QM40-RM1
Connecting the climate system
When connecting to a system with thermostats on all
radiators/underfloor heating coils, a relief valve must
be fitted, or a thermostat must be removed to ensure
sufficient flow.
-FL2
-CM1
-EB15
-XL1
-XL2
15Chapter 4 | Pipe connectionsNIBE™ VVM 310

Other manuals for Nibe VVM 310

Related product manuals