Commissioning without heat pump
The indoor module can be run without heat pump, as
only an electric boiler, to produce heat and hot water,
for example before the heat pump is installed.
Connect the pipe for docking in from the heat pump
(XL8) with the pipe out from the heat pump (XL9).
Enter menu 5.2.4 System settings and deactivate the
heat pump.
NOTE
Select operating mode auto or manual when
the indoor module is to run with the heat
pump.
Pump speed
Both the circulation pumps in VVM 310 are frequency
controlled and set themselves using control and extern-
al heating requirement.
In the menu there are two operating modes for the
circulation pumps, "manual" and "auto". If "auto" is
selected, the circulation pumps are controlled automat-
ically by heating and hot water demands.
LEK
Available pressure, circulation pump, GP1
0
10
20
30
40
50
60
0
200
400
600 800 1000 1200 1400 1600 1800 200
0
Tillgängligt tryck [kPa]
Tillgängligt tryck cirkulationspump, GP1
Available pressure, circulation pump, GP1
Pressure
(kPa)
Flow (l/h)
0
10
20
30
40
50
60
0
200 400 600 800 1000 1200 1400 1600 1800 2000
Tillgängligt tryck cirkulationspump, GP12
Tillgängligt tryck [kPa]
Available pressure, circulation pump, GP1
Available pressure, circulation pump, GP12
Pressure
(kPa)
Flow (l/h)
Post-adjustment, venting
Air is initially released from the hot water and venting
may be necessary. If gurgling sounds can be heard from
the climate system, the entire system will require addi-
tional venting. Vent the installation through the venting
valves (QM20). When venting, VVM 310 must be off.
NIBE™ VVM 310Chapter 6 | Commissioning and adjusting32