AD3000 3 Ethernet
NIDEC ASI S.P.A. AD3000 COMMUNICATION MANUAL
IMAD30007EN 13
3 Ethernet network parameters configuration
3.1 Introduction
The Ethernet network is not a fieldbus but it is at a lower level in the OSI model, where the fieldbuses are at a higher level.
The Ethernet network is a common part that manages basic functions for many of the fieldbuses described in this Communication Manual.
The BASIS control board can be connected to a fieldbus that uses the Ethernet network as a physical medium by inserting an optional board as
specified below:
Modbus TCP by inserting the PROFIBUS DP and Modbus TCP communication module (ETH-PROFI board)
PROFINET IO by inserting the PROFINET IO communication module (GB40A-PROFINET board)
EtherNet/IP by inserting the EtherNet/IP communication module (GB40A-EtherNet/IP board)
For the use of each one of these boards, see the specific paragraph.
The configuration of the parameters of the Ethernet network it is necessary for all fieldbuses that use it, i.e. Modbus TCP, PROFINET IO and
EtherNet/IP. In all these cases it is necessary to configure the Ethernet parameters: IP address, Mask and Gateway.
3.2 Physical interface
Every optional board of the fieldbuses that use Ethernet network has one or more RJ45 connectors to connect cables.
WARNING
In order to avoid any possible failure to the PC Ethernet port connected to the drive, PAY ATTENTION to the label on the ports of the board.
3.3 Network interface configuration
The Ethernet TCP/IP configuration parameters f fall under the ETHERNET TCP/IP [88.00] family.
The default IP address of the board is 192.168.1.1 and the subnet mask is 255.255.255.0.
While connecting the board to a network, the IP address and subnet mask must be modified according to the network configuration.
The IP and subnet mask can be changed both with the DVM and the keypad by modifying the following parameters:
For the IP address:
IP Address-Octet 1 [88.11]
IP Address-Octet 2 [88.12]
IP Address-Octet 3 [88.13]
IP Address-Octet 4 [88.14]
The IP address is modified only after parameter IP Address-Octet 4 [88.14] has been changed.
For the subnet mask:
Subnet mask-Octet 1 [88.15]
Subnet mask-Octet 2 [88.16]
Subnet mask-Octet 3 [88.17]
Subnet mask-Octet 4 [88.18]
The subnet mask is modified only after parameter Subnet mask-Octet 4 [88.18] has been changed.
For the default gateway:
Default Gateway-Octet 1 [88.21]
Default Gateway-Octet 2 [88.22]
Default Gateway-Octet 3 [88.23]
Default Gateway-Octet 4 [88.24]
The default gateway is modified only after parameter Default Gateway-Octet 4 [88.24] has been changed.