Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Running the
motor
Drive parameters Communications
Diagnostics Technical data
UL Listing
Information
Commander S100 User Guide 105
E018 Tune Interrupted
The drive was prevented from completing an auto-tune, because either the drive enable or the drive run signals were
removed.
Recommended actions:
Ensure the drive enable signal is active for the entire auto-tune. This can be checked using Sequencer Input and
Output Indicators (P1.11)
Ensure a run signal (Run Forward, Run Reverse or Run) is active for the entire auto-tune. This can be checked using
Run & Direction Indicators (P1.12)
If these signals are supplied by a digital input, check the states of the IO using Digital IO Indicators (P1.25)
E020 Motor Temp
The drive has estimated that the motor has become too hot based on the Motor Rated Current (P3.01) and Thermal
Protection Action (P3.21).
Motor Thermal Percentage (P1.22) displays the motor temperature as a percentage of the maximum value. The error
occurs when this parameter reaches 100 %.
Recommended actions:
Ensure the load is not jammed / sticking
Check the load on the motor has not changed
Ensure the motor rated current is correct.
E021 Drive Temp 1
An IGBT junction over-temperature has been detected.
Recommended actions:
Check enclosure temperature
Check enclosure / drive fans are still functioning correctly
Clean the fan filter if being used
Check enclosure ventilation paths
Check enclosure door filters
Increase ventilation
Reduce duty cycle
Increase acceleration / deceleration rate parameter values
Reduce motor load
Ensure all three supply phases are present and balanced
Confirm the drive is correctly sized for the application
Use a drive with larger current / power rating
E023 Drive Temp 2
A power stage over-temperature has been detected.
Recommended actions:
See Drive Temp 1
E027 Drive Temp 3
A D.C. bus component over temperature has been detected.
Recommended actions:
See Drive Temp 1.
E028 An In 1 Current
A current loss was detected in T2 analog input 1 and the input type is set to 4-20 mA Error (6). Loss of input is detected if
the current falls below 3 mA.
Recommended actions:
Check control wiring is correct
Check control wiring is undamaged
Check T2 Analog Input 1 Type (P6.01)
Check the current signal is present and greater than 3 mA
Error Diagnosis

Table of Contents