Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Running the
motor
Drive parameters Communications
Diagnostics Technical data
UL Listing
Information
Commander S100 User Guide 107
E172 Fire Mode Error
Fire mode has been deactivated and errors were suppressed while the drive was in fire mode. See Error History 1 (P1.30)
to Error History 3 (P1.32).
E189 An In 1 Overload
The input current on T2 analog input 1 has exceeded 24 mA.
Recommended actions:
Check control wiring is correct.
Check control wiring is undamaged.
Check T2 Analog Input 1 Type (P6.01)
E190 An In 2 Overload
The input current on T4 analog input 2 has exceeded 24 mA.
Recommended actions:
Check control wiring is correct.
Check control wiring is undamaged.
Check T4 Analog Input 2 Type (P6.02)
E216 Firmware Fault 1
Hardware fault - Contact the supplier of the drive.
E220 Firmware Fault 2
Hardware fault - Contact the supplier of the drive.
E222 Firmware Fault 3
Hardware fault - Contact the supplier of the drive.
E224 Firmware Fault 4
Hardware fault - Contact the supplier of the drive.
E228 Ground fault
The drive has detected a ground (earth) fault on the motor cable/windings.
Recommended actions:
Check for short circuit to ground (earth) on the output cables
Check the integrity of the motor insulation using an insulation tester
E232 Firmware Fault 5
Hardware fault - Contact the supplier of the drive.
E235 Firmware Fault 6
Hardware fault - Contact the supplier of the drive.
E245 Firmware Fault 7
A firmware update has been interrupted.
Recommended Actions:
Restart the drive.
If the firmware was being downloaded, try again
If the issue persists this could indicate a hardware fault – Contact the supplier of the drive.
E251 Saved Corrupted
This error indicates that parameter data has been corrupted.
Recommended actions:
Restore factory defaults (P4.01)
E252 Database Changed
A firmware update has been interrupted. The firmware has been changed but the project parameter values have been lost.
Recommended actions:
Restore Factory Defaults (P4.01)
Error Diagnosis